Specifications

NOTE: Buildings that are heated and/or cooled must meet the requirements of the International Energy Conservation Code in effect for the building’s final destination. If you select an insulation system that does not meet these minimum requirements, we will add insulation to meet the code when the building is quoted.

Ceiling

The metal ceiling system will consist of 3" deep, 16" wide interlocking panels of nominal 24-guage embossed galvanized steel, factory painted Arctic White. The ceiling system will be supported at its perimeter by concealed angles. The ceiling system will be furnished complete with all necessary connectors and fasteners
- Option R-30:
  • The ceiling will be insulated with 16" wide by 3-1/2" thick R13 unfaced fiberglass insulation laid in panel void. A 1/4" layer of continuous, reflective, polyethylene insulation (R-7.55, U-0.13) will be laid on top of the ceiling panel ribs. A second layer of 16" wide by 3-1/2" thick R13 unfaced fiberglass insulation will be laid on top at right angles to the panel ribs. The "U" value through the finished ceiling will be a maximum of 0.04 BTU’s per square foot when calculated in accordance with the "Zone Method" contained in ASHRAE "Handbook of Fundamentals", 1981 edition. Clear height = eave height – 6" (single slope type buildings), eave height – 9" (gable type buildings).
- Option R-38
  • The ceiling will be insulated with 16" wide by 3-1/2" thick R13 unfaced fiberglass insulation laid in panel void. A 1/4" layer of continuous, reflective, polyethylene insulation (R-7.55, U-0.13) will be laid on top of the ceiling panel ribs. A second layer of 16" wide by 3-1/2" thick R13 unfaced fiberglass insulation will be laid on top at right angles to the panel ribs. A third layer of 16" wide by 3-1/2" thick R13 unfaced fiberglass insulation will be laid on top, parallel to the ceiling panel ribs. The "U" value through the finished ceiling will be a maximum of 0.032 BTU’s per square foot when calculated in accordance with the "Zone Method" contained in ASHRAE "Handbook of Fundamentals", 1981 edition. Clear height = eave height – 8" (single slope type buildings), eave height – 11" (gable type buildings).
- Option R-49
  • The ceiling will be insulated with 16" wide by 3-1/2" thick R13 unfaced fiberglass insulation laid in panel void. A 1/4" layer of continuous, reflective, polyethylene insulation (R-7.55, U-0.13) will be laid on top of the ceiling panel ribs. A second layer of 16" wide by 3-1/2" thick R13 unfaced fiberglass insulation will be laid on top at right angles to the panel ribs. A third layer of 16" wide by 3-1/2" thick R13 unfaced fiberglass insulation will be laid on top, parallel to the ceiling panel ribs. A fourth layer of 16" wide by 3-1/2" thick R13 unfaced fiberglass insulation will be laid on top at right angles to the panel ribs. The "U" value through the finished ceiling will be a maximum of 0.025 BTU’s per square foot when calculated in accordance with the "Zone Method" contained in ASHRAE "Handbook of Fundamentals", 1981 edition. Clear height = eave height – 11" (single slope type buildings), eave height – 13" (gable type buildings).

Blanket Roof Insulation

Roof insulations will consist of 48" wide, 3" thick, 6# density fiberglass faced on its exposed side with a white metalized polypropylene scrimkraft facing. The faced insulation material will have a UL Flame Spread Rating of 26 when tested in accordance with UL 723 ASTM E procedures. Insulation will be supported at the roof line by means of mechanical clips spaced on maximum 4’-0" centers and will be sealed by means of 2" side tab on facing.

Therma-Roof

The Therma-Roof insulation system will consist of two layers of 1-1/2" thick, 48" wide polyisocyanurate foam board faced with a white embossed foil on the exposed interior surface. The roof insulation system will include metal supporting tees on 4’ centers and all trim required for a finished interior appearance. No metal-to-metal contact between the insulation system and exterior roof or wall covering will be permitted. The insulation will have a maximum UL flame Spread Rating of 25, Fuel contributed Rating of 10 and Smoke Developed Rating of 155-190 when tested in accordance with UL 723 testing methods and will meet the requirements of the Underwriters Laboratories "Wall-Ceiling" Construction Classification.

Drawings

Drawing Name Rev Description Type
A-CAL-C 0 Ceiling System for Gable Buildings Approval
A-CAL-R30 1 Ceiling System for Gable Buildings Approval
A-CAL-R38 1 Ceiling System for Gable Buildings Approval
A-CAL-R49 0 Ceiling System for Gable Buildings Approval
A-CALP-R30 0 Perforated Ceiling System for Gable Buildings Approval
A-CALP-R38 0 Perforated Ceiling System for Gable Buildings Approval
A-CALP-R49 0 Perforated Ceiling System for Gable Buildings Approval
A-CS-14 0 Ceiling for Single Slope Building Approval
A-CS-C 1 Support System For Ceiling Approval
A-CS-R30 0 Ceiling for Single Slope Building Approval
A-CS-R38 0 Ceiling for Single Slope Building Approval
A-CS-R49 0 Ceiling for Single Slope Building Approval
A-CSP-R30 0 Perforated Ceiling for Single Slope Building Approval
A-CSP-R38 0 Perforated Ceiling for Single Slope Building Approval
A-CSP-R49 0 Perforated Ceiling for Single Slope Building Approval
A-RIAL-3 0 3" Thick Faced Roof Insulation With Stick Clips Approval
A-RIAL-4 0 4" Thick Faced Roof Insulation With Stick Clips Approval
A-RIAL-6 0 6" Thick Faced Roof Insulation With Stick Clips Approval
A-RIS-3 0 3" Faced Roof Insulation With Stick Clips Approval
A-RIS-4 0 4" Faced Roof Insulation With Stick Clips Approval
A-RIS-6 0 6" Faced Roof Insulation With Stick Clips Approval
A-TRAL 0 3" Therma Roof Insulation System Approval
A-TRS 0 Therma Roof Insulation System Approval
200209 5 Blanket Roof Insulation With Wire Mesh Erection
A48-AL-NT 3 A48 Acoustical Wall Liner System Installation Erection
A48-S-NT 4 A48 Non Tested Acoustical Wall Liner System Details Erection
A49-AL 6 A49 Acoustical Wall Liner System Installation Erection
A49-S 6 A49 Acoustical Wall Liner System Details Erection
CEIL-ACC 1 OPTIONAL CEILING ACCESSORIES Erection
CEIL-AL-1 7 Full Height Ceiling Installation For Type 'AL' Buildings And No Equipment Supports Erection
CEIL-AL-2 9 Dropped Height Ceiling Installation For 16'-0" And Smaller Type ' AL' Buildings With Equipment Supports Erection
CEIL-AL-3 5 Dropped Height Ceiling For 20'-0" And Wider Type 'AL' Buildings With Equipment Supports Erection
CEIL-AL-4 5 Dropped Height Ceiling For 20'-0" And Wider Type 'AL' Buildings With Equipment Supports Same Height As Ceiling Panel Erection
CEIL-AL-STIF 3 Ceiling Reinforcement For Type 'AL' Building Erection
CEIL-R30 2 R30 Ceiling Insulation Detail Erection
CEIL-R38 2 R38 Ceiling Insulation Erection
CEIL-R49 2 R49 Ceiling Insulation Erection
CEIL-S14 1 Ceiling Installation For Type 'S' Buildings With 1/4" in 12" Roof Slope And Any Ceiling Height Erection
CEIL-S14-PE1 1 Ceiling Installation For Type 'S' Building With 1/4" In 12" Roof Slope, Standard Height Ceiling And 'Drop' Wall Cap Erection
CEIL-S14-PE2 1 Ceiling Installation For Type 'S' Building With 1/4" In 12" Roof Slope, Dropped Ceiling And Short 'Drop' Wall Cap Erection
CEIL-S14-STIFF 1 Ceiling Reinforcement For Type 'S' Building Erection
HM-CEIL 3 1 And 2 Hour Fire Ceiling Details Erection
RFINS-AL 2 Blanket Roof Insulation With Stick Clips Erection
RFINS-S 2 Roof Insulation with Stick Clips Erection
TR-AL-1 1 Therma-Roof Insulation System Installation Erection
TR-AL-2 2 Therma-Roof Insulation System Installation Erection
TR-AL-3 3 Therma-Roof Insulation System Installation Erection
TR-AL-4 2 Therma-Roof Insulation System Installation Erection
TR-S-1 2 Therma-Roof Insulation System Installation Erection
TR-S-2 2 Therma-Roof Insulation System Installation Erection
TR-S-3 2 Therma-Roof Insulation System Installation Erection
13122A48 1 A48 Acoustical Wall SpecSheet
13122CEL 0 Ceiling SpecSheet
13122CEL30 0 CEILING WITH R30 INSULATION SpecSheet
13122CEL38 0 CEILING WITH R38 INSULATION SpecSheet
13122CEL49 0 CEILING WITH R49 INSULATION SpecSheet
13122RI 1 Roof Insulation SpecSheet